Self-healing shunt capacitor YC111-D Cylinder Type, low loss, excellent performent and long life. Small volume, light weight

CNC Low Voltage Self-healing Shunt Power Capacitor YC111-D

ConstructionDielectric:Polypropylene filmdry typeWave cutExtruded round aluminum can with threadedProtection:IP20

Single phase or three phase on requested

Features

Three phase,delta connected.With discharge resistorSelf-healing technology,overpressure disconnectorNaturally air cooled(or forced air cooling)Indoor mountingfile#E307252

Technical characteristics

 

Technical data and specification

Charateristics

  

Rated capacitance CRand QR

According to specification table

Tolerance

-5/+10%

Connection

D(Delta)

Rated voltage VR

According to specification table

Rated frequency fR

50/60Hz

Maximum ratings(to IEC 60831)

Maximunm permissible voltage Vmax

VR+10%(up to 8 h daily)VR+15%(up to 30 min daily)VR+20%(up to 5 min daily)VR+30%(up to 1 min daily)

Maximum permissible current Imax

Up to 1.3×IRincl.combined effects of harmonics,over voltages and capacitance)

Maximum transient inrush current

Up to 200×IR

Power dissipation (dielectric)

<0.2 W/kvar

Power dissipation(excluding discharge resistors)

<0.45 W/kvar

Test data(accord. to IEC 60831)

AC test voltage terminal-to-terminal

2.15×VR,2s

Insulation voltage between terminalsand container

3000V AC, 10s

Dissipation factor tanδat 100Hz

≤1.0×10-3

Climatic category/-40/D

Tmin (-)

Tmax (+)

Humidity

av.rel.<95%

Maimun altitude

4000m

Mean life expectancy

tLD (-)

Max. 5000 switching per year acc. to IEC 60831

Safety

Mechanical

Overpressure disconnector

Max.

(AFC:10000)

Discharge

≤3 min (75V)

Reference standards

IEC 60831-1/2. UL 810-5th edition

self-healing shunt capacitor